N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
Actuators: LF24-ECON-R03 US LF24-ECON-R10 US AF24-ECON-R03 US
Actuators with plenum rated cable do not have numbers on
wires; use color codes instead. Actuators with appliance
cables are numbered.
5
Equipment damage!
Actuators may be connected in parallel. Power consumption
and input impedance must be observed.
2
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
INSTALLATION NOTES
26
Min-position is adjustable from 0 to 100% with a
potentiometer on the actuator cover.
27
A relay or switch can spring return the actuator when the
RTU fan de-energizes, or if low ambient temperature is sensed.
28
A standard relay can be used to close the sensor circuit to
engage economizer mode, e.g. outside air changeover device
like a dry bulb or enthalpy limit switch. Honeywell logic
module W7459A and enthalpy sensor C7400 also provide
terminals for this switching.
29
A remote CO2 sensor or DDC controller can change the
standard relay opening or closing the sensor circuit. This
device can be a relay or a dry bulb/enthalpy limit switch.
30
30
Override control for Y2 only accepts 0 to 10 VDC
override control.
W202
W203
24 VAC Transformer
Line
Volts
3 kΩ NTC*
MA thermistor
setpoint 55F
Blk (1) Common
Red (2) + Hot
Wht (3) Y
1
Org (4) Y
2
Min-pos, 0 to 10 V
Grn (5) U Output, 2 to 10V
Default
CW CCW
0
.2
.4
.6
.8
1
MIN
LF24-ECON-R03 US
LF24-ECON-R10 US
27
28
29
27
29
5
Standard Economizer Mode Wiring
Override
Override Control
Wire
AF24-ECON
LF24-ECON… position
ApplicationInput Signal
Y1 24 VAC Drive closed (0%)
Morning warm-up cycle
Y1 Common Drive open (100%) Smoke Purge
Y1 Open wire Drive to min. position Mechanical cooling in
use, RTU thermostat
calls for heat.
Y2 0 VDC to 10 VDC Min. position of 0% to 100%
Override potentiometer
via a remote C02
sensor/controller or
DDC controller.
24 VAC Transformer
Line
Volts
Blk (1) Common
Red (2) + Hot
Wht (3) Y
1
Org (4) Y
2
Min-pos, 0 to 10V
Grn (5) U Output, 2 to 10V
Default
CW CCW
0
.2
.4
.6
.8
1
MIN
A
A
B
B
Override
Closed (0%)
Override
Open (100%)
5
0 to 10 VDC
(–)
(+)
Control Signal
(–)
(+)
Control Signal
0 to 10 VDC
AF24-ECON-R03 US
LF24-ECON-R03 US
LF24-ECON-R10 US
AF24-ECON-R03 US
26
26
2
30
2
*10 kΩ NTC thermistor for -R10 types.
®
W604_11
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical
components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical
components perform these tasks. Failure to follow all electrical
safety precautions when exposed to live electrical components
could result in death or serious injury.
Wiring for Damper Actuators and Control Valves
Proportional, Spring Return, 24V, 3 kΩ or 10 kΩ Control Input