Vista de pagina 19
800-543-9038 USA 866-805-7089 CANADA 203-791-8396 LATIN AMERICA / CARIBBEAN
20
N40067 - 7/11 - Subject to change. © Belimo Aircontrols (USA), Inc.
Blk (1) Common
Red
(2) + Hot
Wht
(3) Y
Input
Org (5) U
Output
Pnk (4) Y
2
Input
Line
Volts
24 VAC Transformer (AC only)
(+)
(–)
4
Position
Feedback VDC
8
9
Contact closures A & B also can be triacs. A & B should
both be closed for triac source and open for triac sink.
7
Blk
(1)
Common
Red
(2)
+ Hot
Pnk
(4)
Y
2
Input
Wht
(3)
Y
1
Input, 2 to 10V
Grn
(5)
U
Output, 2 to 10V
(–)
(+)
Line
Volts
24 VAC Transformer
VDC/4-20 mA
Ω
500 Ω
1/4 watt
PWM (except NKQ)
Triac Source and Sink Diagrams (See page 21)
Floating Point (except NKQ)
Two Position
Override Control to min, mid, max, Positions
Functions
0%
50%
100%
Control mode acc. to Y
Min*
Mid*
Max*
Normal**
* Default selectable 0-100%. See Configuration Data Sheet.
** Customizable. See Configuration Data Sheet.
a bc
500 Ω
Ω
Blk
(1)
Common
Red
(2)
+ Hot
Pnk
(4)
Y
2
Input
Org
(5)
Wht
(3)
Y
1
Input, 2 to 10V
(–)
(+)
Line
Volts
24 VAC Transformer (AC Only)
7
3
B
C
A
1/4 watt
3 54
CCW CW
Actuators:
EFB24-MFT(-S) EFX24-MFT(-S) AFB24-MFT(-S) AFX24-MFT(-S) NFB24-MFT(-S) NFX24-MFT(-S)
LMX LRX NMX AMX ARX GKX NKQ ARX24-MFT-5 ARB24-MFT-5 GRX24-MFT-5
GMX24-MFT-X1 GRB24-MFT-S GRB24-MFT-5 GRB24-MFT-7
Actuators with plenum rated cable do not have numbers on
wires; use color codes instead. Actuators with appliance
cables are numbered.
3
Actuators may also be powered by 24 VDC.
5
Meets cULus requirements without the need of an electrical
ground connection.
8
Equipment damage!
Actuators may be connected in parallel if not mechanically
mounted to the same shaft. Power consumption and input
impedance must be observed.
4
CAUTION
Indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury. It may also be used to
alert against unsafe practices.
Warnings and Cautions appear at appropriate sections throughout
this manual. Read these carefully.
Hazard Identification
INSTALLATION NOTES
APPLICATION NOTES
Control signal may be pulsed from either the Hot (Source)
or Common (Sink) 24 VAC line.
10
For triac sink the Common connection from the actuator
must be connected to the Hot connection of the controller.
Position feedback cannot be used with a triac sink controller.
The actuator internal common reference is not compatible.
7
A 500 Ω resistor converts the 4 to 20 mA control signal
to 2 to 10 VDC.
CCW
CW
AB
5
CCW
CW
AB
5
Direction of rotation switch
Line
Volts
(–)
(+)
24 VAC Transformer
Blk
(1)
Common –
Red
(2)
Hot +
Wht
(3)
Y
1
Input
Org
(5)
U
Output 2 to 10V
Pnk
(4)
Y
2
Input
8
34
A
B
9
10
Blk (1) Common
Red
(2) Hot
Pnk
(4) Y
2
Input
Wht
(3) Y Input
Org
(5) U Output
Line
Volts
24 VAC/DC Transformer
a
Position
Feedback VDC
(+)
(–)
4 3
Control Signal
4 to 20 mA or 2 to 10 VDC
2 to 10 VDC
Feedback Signal
2-10 VDC or 4 to 20 mA
Control Signal
5
5
5
5
W400_A_11
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may
be necessary to work with live electrical components. Have a qualified licensed
electrician or other individual who has been properly trained in handling live
electrical components perform these tasks. Failure to follow all electrical safety
precautions when exposed to live electrical components could result in death or
serious injury.
Wiring for Damper Actuators and Control Valves
MFT, Spring Return, Non-Spring Return, Electronic Fail-Safe, 24V